1. Sub metering

Mr. Alok,

For sub metering of any residential applications, a 1/2" single jet meter should be alright since it does not hold small contaminations in the meter and the meter has a nominal flow rate of 1500 lph which is more than enough. Nominal flow rate is the flow rate at which the meter gives good accuracy.

Regards

Venkatesh